Low-load position fuel B [Digit]

Parameter

Description

A fuel is activated and shut down using the parameterized low-load positions for fuel A and B for this simultaneous firing operation mode, not the low-load positions of the individual operation modes. When a fuel is changed without load dropping, the low-load positions of the single operation modes can be used because the low-load positions of the single operation mode correspond to the low-load positions of the individual fuels. The low load position of a simultaneous firing operation mode corresponds to the sum of the low load positions of the individual fuels but not necessarily to a fuel ratio of 50 %.

For operation modes with simultaneous firing, the low-load position for fuel B must be entered here. Depending on the parameterization, fuel B is fuel 2 or 3.

Properties

Type

Integer

Min

0

Max

2000

Unit

Digit

Reference

2155; 2183; 2211; 2239; 2267; 2295; 2323; 2351

DOC-729016386