Operation mode
Activate fuels
Load shut-off limit during burner stop
Channel selection for this operation mode
Burner direct start / direct stop
Start additional fuel as of load position
Stop additional fuel as of load position
Primary fuel
Load position MAX start secondary fuel
Load position MIN start secondary fuel
Low-load position fuel A [Digit]
Low-load position fuel B [Digit]
Pilot Burner Function
Operation mode selected
Parameter
Description
A fuel is activated and shut down using the parameterized low-load positions for fuel A and B for this simultaneous firing operation mode, not the low-load positions of the individual operation modes. When a fuel is changed without load dropping, the low-load positions of the single operation modes can be used because the low-load positions of the single operation mode correspond to the low-load positions of the individual fuels. The low load position of a simultaneous firing operation mode corresponds to the sum of the low load positions of the individual fuels but not necessarily to a fuel ratio of 50 %.
For operation modes with simultaneous firing, the low-load position for fuel A must be entered here. Depending on the parameterization, fuel A is fuel 1 or 2.
Properties
Integer
0
2000
Digit
See also
Reference
2154; 2182; 2210; 2238; 2266; 2294; 2322; 2350
DOC-729016270