Compound
Current burner load
Load curve: Current position
Burner load: Physical scaling
Burner load: Physical unit
Full load: Load position
Full load: Physical value
Minimum running time of compound control
Load setpoint response threshold
Dynamik Test
Fuel and Air Setpoints for Load Changes
Maximum load difference fuel > air
Minimum load difference air > fuel
Maximum load difference air > fuel
Load setpoint Overshoot
Parameter
Description
x = Minimum load difference air > fuel + 1
Defines the maximum load difference by which the air setpoint can exceed the fuel setpoint.
This value must not be less than 10 digits.
Adjust the Maximum load difference air > fuel and Minimum load difference air > fuelat a ratio of 2 to 1
* Factory settings
Properties
Integer
x
100
Digit
See also
Reference
2033
DOC-719749141