..
Main Flame Stabilization
Main flame stabilization compound position
Main flame stabilization time
Load position for flame stabilization
Release load control without low load position
Parameter
Description
This function is used for controlled lifting of the main flame following the burner start for TEMINOX burners with reaction chamber.
If the value 0 is parameterized, the function is deactivated.
Defines whether the compound for flame stabilization of liquid fuels moves to the set load position after fuel 1 or fuel 2 has been ignited and the low-load position has been reached.
Only active if Main flame stabilization compound position = "[0] In low-load position".
Main flame stabilization time must be adjusted such that the compound reaches the adjusted load position. Load control is released after the main flame stabilization time interval plus 3 seconds has elapsed. The load control is updated during flame stabilization and starts at the current load position following control release.
Properties
Integer
0
50
%
See also
Reference
2111
DOC-719499400