After the HMI program is updated, information indicating problems loading the configuration appears when the old configuration is loaded and directly when the HMI is started. You can ignore this information. The same applies to the representation of the save symbol in the header of the HMI.
After the HMI program is updated, the configuration must always be saved once on the HMI. Loading the configuration should then no longer trigger a fault message.
In the following table, when updating the HMI program, all version information that is reached or skipped must be taken into account.
Example
HMI: HMI05e
Old version: V3.22.00.00
New version: V3.32.08.00
Version information to be considered: V3.24.06.00, V3.30.00.00, V3.32.08.00
Version |
Hints |
V3.16.00.00 |
A complete verification of the configuration is required. |
V3.24.06.00 |
HMI10e / HMI05e: Minimum required operating system version: V3.22.00. |
V3.24.18.00 (HMI03) |
If you updating from V3.20.00.00 or higher: The DCS bits "Send 7.10" and "Send 7.11" are inverted. |
If both the DFT function and the internal load control are used, the control behavior of the load controller must be checked. |
|
V3.30.00.00 |
Changes to the operator documentation. An update to this version may require the documents to be re-issued to the customer. |
V3.32.08.00 |
If both the DFT function and the internal load control are used, the control behavior of the load controller must be checked. |