Simultaneous firing: Stabilization time F3

Parameter

Description

The stabilization time for simultaneous firing is used to delay the control release of the added fuel. The fuels will remain in the connection position until the stabilization time has elapsed. This function is used, e.g. for pulverized coal firing systems to ensure the ignition of the carbon. After the stabilization time has elapsed, the added fuel will be granted controlled release and the ignition fuel will be run to the low-load position and switched off.

Properties

Type

Integer

Min

0

Max

3600

Unit

Seconds

Reference

2106

DOC-729429317