Correction signal 2: Safety shut-off hardware fault

Parameter

Description

The safety shut-off is triggered if

  • the communication to the FSC-IO 4DI/1AI module is faulty or

  • the FSC-IO 4DI/1AI module detects an assembly fault or

  • the correction signal detects a wire breakage.

A safety shut-off is triggered when a hardware fault is detected.

The safety shut-off is disabled if the correction signal is sent from the HMI (Correction signal 1: Source) via the bus system.

Properties

Type

Yes/No

[Yes]

The burner safety shut-off is triggered if a hardware fault is pending on one of the input modules (FSC-IO 4DI/1AI).