Correction signal 2: Input signal

Parameter

Description

Inverts the effect of the physical input signals.

The table below shows examples of the required input current for different zero points with and without inversion:

Zero point Not inverted Inverted
0 % 4 mA 20 mA
25 % 8 mA 16 mA
30 % 8.8 mA 15.2 mA
50 % 12 mA 12 mA
60 % 13.6 mA 10.4 mA
80 % 16.8 mA 7.2 mA
100 % 20 mA 4 mA

Example

Zero point 80 % and correction signal not inverted:

4 mA + (20 mA – 4 mA) / 100 % * 80 % = 16.8 mA

Zero point 80 % and correction signal inverted:

20 mA – (20 mA – 4 mA) / 100 % * 80 % = 7.2 mA

Properties

Type

Selection parameter

[0] Not inverted (4 - 20 mA = 0 - 100 %)
[1] Inverted (4 - 20 mA = 100 - 0 %)

Reference

1045

DOC-729426176