Correction signal 1: Zero point at

Parameter

Description

Adjusts the correction signal zero point between 0 and 100 %. The maximum correction influence is subdivided according to the adjusted zero point.

0 % Only positive correction 0 – 100% at 4 – 20mA Zero correction at 0mA
50 % Negative and positive correction -50 – 50% at 4 – 20mA Zero correction at 12mA
100 % Only negative correction 0% at 4 – 20mA Zero correction at 20mA

The table below shows examples of various zero points:

Zero point Minimal correction Maximum correction
0 % 0 % 100 %
25 % -25 % 75 %
30 % -30 % 70 %
50 % -50 % 50 %
60 % -60 % 40 %
80 % -80 % 20 %
100 % -100 % 0 %

Properties

Type

Integer

Min

0

Max

100

Unit

%

Reference

2380

DOC-729175781