O2: Automatic alarm reset

Parameter

Description

Prerequisite:

  • The burner is being started

or

  • The burner is in operation (firing) and

  • one of the O₂ alarms MIN1, MIN2, MAX or dynamic probe test has been triggered and

  • the O₂ actual value is within the MIN1 and MAX limits and the O₂ alarm is pending for at least the Delay time - control release, but for at least 45 seconds.

Properties

Type

Yes/No

[Yes]

O₂ alarm is automatically reset.

Reference

1060

DOC-729171648