O2 monitoring (alarms)
O2: Monitoring during purging / after ignition
O2: Monitoring of MIN1, MIN2 and MAX alarms
O2: Limit value alarm MAX
O2: Delay time for alarm MAX
O2: Limit value alarm MIN1
O2: Delay time for alarm MIN1
O2: Limit value alarm MIN2
O2: Delay time for alarm MIN2
O2: Safety shut-off at alarm MIN2
O2: Monitoring dynamic probe test
O2: Limit value probe dynamics test 1
O2: Limit value probe dynamics test 2
O2: Automatic alarm reset
Parameter
Description
Entering 0 to 20 vol.% corresponds to 0 to 2000 as a parameter value.
Defines the limit value for the probe dynamics test 1.
The measured O₂ value is monitored for changes during operation. If no fluctuations greater than ± 0.1 vol. % O₂ are detected over a period of 10 minutes, then the probe dynamics test is performed based on the current setting value of the O₂ controller with excess air (setting value ≤ 0%) or air deficiency (setting value > 0 %).
In the dynamic test, an air excess or air deficiency of 33% is forced. If no change in the measured O₂ value is detected after one minute, the value is increased to 66%. If a change cannot be detected after another minute, the value is increased to 99%. If there is still no change in the measured O₂ value, an alarm is triggered and O₂ correction is deactivated. The excess air or air deficiency is limited to the defined maximum O₂ correction value.
Properties
Floating point
0
20
Vol.%
Reference
2037
DOC-729171291