O2 monitoring (alarms)
O2: Monitoring during purging / after ignition
O2: Monitoring of MIN1, MIN2 and MAX alarms
O2: Limit value alarm MAX
O2: Delay time for alarm MAX
O2: Limit value alarm MIN1
O2: Delay time for alarm MIN1
O2: Limit value alarm MIN2
O2: Delay time for alarm MIN2
O2: Safety shut-off at alarm MIN2
O2: Monitoring dynamic probe test
O2: Limit value probe dynamics test 1
O2: Limit value probe dynamics test 2
O2: Automatic alarm reset
During burner operation, the O₂ actual value is constantly monitored for a maximum limit value (Alarm MAX) and two minimum limit values (Alarm MIN 1 and Alarm MIN 2).
O₂ monitoring bands
Load position in digits
O₂ setpoint in vol%
O₂ setpoint
Alarm MAX
Alarm MIN 1
Alarm MIN 2
The limit values are specified in percent based on the current O₂ setpoint. If the O₂ setpoint
decreases, the difference between the O₂ setpoint and the limit values decreases.
increases, the difference between the O₂ setpoint and the limit values increases.