O2 correction in operation mode
Used
Correction value low load
Correction value full load
Control release
Control ON as of load position
Control OFF as of load position
O2 correction value for alarm MIN 2
Parameter
Description
In case of an O₂ alarm MIN2, the correction value defined here is added to the load position for each operation mode.
The air volume increase due to the O₂ correction value in case of an O₂ alarm MIN2 must not produce an explosive fuel/air mixture in case of an O₂ deficiency!
If one of the monitors triggers an alarm (except "O₂ alarm MAX"), then O₂ correction is disabled.
All O₂ alarms are saved and must be acknowledged on the HMI.
Properties
Integer
0
2000
Digit
Reference
2052; 2058; 2064; 2070; 2076; 2082; 2088; 2094
DOC-729163776