O2 correction: Control release

O2 control is released when all of the following conditions are met:

  • The burner fires.

  • The delay time for control release Delay time - control release after burner is firing, after a fuel change and after additional fuel activation or deactivation has expired.

  • The burner capacity is within the allowable activation and shut-down limits.

  • The maximum load change does not exceed the value from parameter Deactivation at load difference.

  • O₂ correction was switched on in the operation mode using parameters O2 correction in operation mode: Used.

  • The O₂ setpoint curve was entered completely in the active operation mode.

  • The setup mode is not active.

  • The O₂ alarms for purging, ignition, MIN1, MIN2 and probe are not pending.

  • Flue gas recirculation has been released when a channel with flue gas recirculation is active in the operation mode.

Note

O₂ correction is only released for the active operation mode when all saved load points have been assigned to an O₂ setpoint.

DOC-729162462