O2 correction in operation mode
Used
Correction value low load
Correction value full load
Control release
Control ON as of load position
Control OFF as of load position
O2 correction value for alarm MIN 2
O2 control is released when all of the following conditions are met:
The burner fires.
The delay time for control release Delay time - control release after burner is firing, after a fuel change and after additional fuel activation or deactivation has expired.
The burner capacity is within the allowable activation and shut-down limits.
The maximum load change does not exceed the value from parameter Deactivation at load difference.
O₂ correction was switched on in the operation mode using parameters O2 correction in operation mode: Used.
The O₂ setpoint curve was entered completely in the active operation mode.
The setup mode is not active.
The O₂ alarms for purging, ignition, MIN1, MIN2 and probe are not pending.
Flue gas recirculation has been released when a channel with flue gas recirculation is active in the operation mode.
O₂ correction is only released for the active operation mode when all saved load points have been assigned to an O₂ setpoint.
DOC-729162462