O2 correction
O2 correctin value scaling
O2 correction in operation mode
O2 monitoring (alarms)
Delay time - control release
Deactivation at load difference
Permit deactivation by the HMI
O2 measuring system OXYPro
O2 control compensates for interference variables which have a negative effect on the fuel-air ratio. The combustion air is subject to temperature, humidity and pressure fluctuations. The fuel is subject to temperature, heat value and pressure fluctuations.
For each operation mode, O₂ correction can be activated separately and an individual O₂ setpoint curve can be entered based on the burner capacity. The O₂ correction influences the load position of the air or fuel channels parameterized via the channel functions.
The O₂ controller receives its setpoint from the specified O₂ setpoint curve based on the current load position. From the setting value of the O₂ controller (-100.0 % to +100.0 %), the current load position, the O₂ correction value at low load and the O₂ correction value at full load the O₂ correction for the load position is calculated.
O₂ correction should act on the air ducts. If the plant uses fans with speed control, then O₂ correction must be used for speed control and for the corresponding damper. O₂ correction may only act on either the air or the fuel channels for each operation mode.
O2 correction value
Load position
Channel position
Air channel
O₂ correction max
O₂ correction min
See also
Channel function
DOC-729158097