Compound
Current burner load
Load curve: Current position
Burner load: Physical scaling
Burner load: Physical unit
Full load: Load position
Full load: Physical value
Minimum running time of compound control
Load setpoint response threshold
Dynamik Test
Fuel and Air Setpoints for Load Changes
Maximum load difference fuel > air
Minimum load difference air > fuel
Maximum load difference air > fuel
Load setpoint Overshoot
The fuel and air setpoints are calculated with regard to the maximum load difference.
In case of a load increase, the load setpoint of the air channels is increased first, then the load setpoint of the fuel channels.
In case of a load reduction, the fuel channel load setpoint is reduced first, then the load setpoint of the air channels.
This ensures that there is always an excess of air in the event of significant load changes.