Compound
Current burner load
Load curve: Current position
Burner load: Physical scaling
Burner load: Physical unit
Full load: Load position
Full load: Physical value
Minimum running time of compound control
Load setpoint response threshold
Dynamik Test
Fuel and Air Setpoints for Load Changes
Maximum load difference fuel > air
Minimum load difference air > fuel
Maximum load difference air > fuel
Load setpoint Overshoot
Parameter
Description
Defines the minimum running time of the compound. The compound running time is used for all the operation modes.
The compound running time is used to set the setting speed between the minimum (0%) and maximum (100%) load position. The compound running time is used for all the operation modes.
Configure the minimum running time of the compound so that it is long enough for the slowest actuator.
If the minimum running time setting is too short, the compound is decelerated repeatedly when load changes occur because the slowest actuator exceeds the tolerance band limits.
Properties
Integer
0
900
s
Reference
2032
DOC-719746859