1st safety time (Ignition flame)

Parameter

Description

0 to 300 corresponds to 0.3 to 30.0 seconds.

The 1st safety time is the time period between the opening of the ignition valves and the activation of the ignition flame monitor. The ignition flame must be formed within the 1st safety time.

The 1st safety time is shown in the form of graphics in the following sequence diagrams:

The value adjusted here must be greater than or equal to the value in Ignition time.

Not active for direct ignition.

Properties

Type

Integer

Min

0

Max

300

Unit

Seconds

See also

Reference

2011

DOC-729092307