Ignition
Igniter
Number of ignition attempts
Main Flame Stabilization
Irrelevance Time of Operation Safety Interlock Circuit
Ignition: External release
Ignition: Status signals
Parameter
Description
Defines the irrelevance time of the operation safety interlock circuit after ignition of the main burner.
The operation safety interlock circuit must be closed within the set irrelevance time after the main fuel valves have been opened (used e.g. for MIN oil pressure with steam pressure atomizers).
If the safety interlock circuit does not close within the delay time, the safety shut-off is triggered with the following message: 116
Properties
Integer
0
10
s
Reference
2028