Irrelevance Time of Operation Safety Interlock Circuit

Parameter

Description

Defines the irrelevance time of the operation safety interlock circuit after ignition of the main burner.

The operation safety interlock circuit must be closed within the set irrelevance time after the main fuel valves have been opened (used e.g. for MIN oil pressure with steam pressure atomizers).

If the safety interlock circuit does not close within the delay time, the safety shut-off is triggered with the following message: 116

Properties

Type

Integer

Min

0

Max

10

Unit

s

Reference

2028

DOC-719739711