Check air pressure monitor

Parameter

Description

Properties

Type

Selection parameter

[0] Check air pressure monitor always

The air pressure monitor is checked before start-up of the combustion air fan.

Within a delay time of 180 seconds, it has to send a signal indicating that there is no combustion air pressure. If this is not the case, a safety shut-off is triggered after the delay time has expired following starting of the purge sequence, with the message (102) "FSC: CAP > MIN before CAF Start".

[1] Check air pressure monitor before fan start

The air pressure monitor check is only performed if the combustion air fan wasn't running (required if a switch-off delay has been set for the combustion air fan).

Within a delay time of 180 seconds, it has to send a signal indicating that there is no combustion air pressure. If this is not the case, a safety shut-off is triggered after the delay time has expired following starting of the purge sequence, with the message (102) "FSC: CAP > MIN before CAF Start".

The operation message of the combustion air fan must be monitored in the safety interlock circuit after fan start-up. If the safety interlock circuit is not included in the FSC input configuration after fan start-up, then monitoring must take place in the following safety interlock circuits:

  • Safety interlock circuit fuel 1

  • Safety interlock circuit fuel 2

  • Safety interlock circuit for atomization

[2] Check air pressure monitor never

The air pressure monitor isn't checked.

You are only allowed to activate this parameter if the applicable standards and regulations permit this.

Reference

1032, 1033, 1034

DOC-729078695