Purge
Delay time of safety interlock circuit before fan start
Combustion air pressure: Relief
Purge: Start: Release
Purge: End: Release
Check air pressure monitor
Purge suppression
Purge time
Post-purging
Post-purge time
Switch-off delay of fan motor
Burner motor operation while post purging
Delay time purge position
Status signals
Parameter
Description
Properties
Selection parameter
The air pressure monitor is checked before start-up of the combustion air fan.
Within a delay time of 180 seconds, it has to send a signal indicating that there is no combustion air pressure. If this is not the case, a safety shut-off is triggered after the delay time has expired following starting of the purge sequence, with the message (102) "FSC: CAP > MIN before CAF Start".
The air pressure monitor check is only performed if the combustion air fan wasn't running (required if a switch-off delay has been set for the combustion air fan).
Within a delay time of 180 seconds, it has to send a signal indicating that there is no combustion air pressure. If this is not the case, a safety shut-off is triggered after the delay time has expired following starting of the purge sequence, with the message (102) "FSC: CAP > MIN before CAF Start".
The operation message of the combustion air fan must be monitored in the safety interlock circuit after fan start-up. If the safety interlock circuit is not included in the FSC input configuration after fan start-up, then monitoring must take place in the following safety interlock circuits:
Safety interlock circuit fuel 1
Safety interlock circuit fuel 2
Safety interlock circuit for atomization
The air pressure monitor isn't checked.
You are only allowed to activate this parameter if the applicable standards and regulations permit this.
Reference
1032, 1033, 1034
DOC-729078695