Purge
Delay time of safety interlock circuit before fan start
Combustion air pressure: Relief
Purge: Start: Release
Purge: End: Release
Check air pressure monitor
Purge suppression
Purge time
Post-purging
Post-purge time
Switch-off delay of fan motor
Burner motor operation while post purging
Delay time purge position
Status signals
Parameter
Description
Duration for which the control dampers of the air channels (secondary air, primary air, cooling air) and the flue gas channels (furnace shut-off damper, furnace pressure control damper) remain open / in the purge position during purging.
The value adjusted here must be ≥ RECI: Delay time purge position.
The purge positions and the combustion air pressure are monitored during purging. A brief interruption (≤ 3 s) of the purging conditions (not a safety shut-off) results in a reset of the purge time.
When setting the purge time, ensure compliance with all the applicable standards and regulations for the firing plant!
Properties
Integer
0
32400
Seconds
See also
RECI: Delay time purge position
Reference
2001
DOC-719771025