Post-purging

Parameter

Description

The "post-purging" option forces purging of the furnace, the flue gas ducts and the flue gas recirculation channel after the burner shut-down. In this way, any residual fuel/air mixture and/or combustion product is blown out. The "post-purging" option forces purging of the furnace, the flue gas ducts and the flue gas recirculation channel after the burner shut-down. In this way, any residual fuel/air mixture and/or combustion product is blown out.

Post-purging only takes place if the ignition, gas or oil valves have been opened and is started immediately after the burner has been shut down. For post-purging, the safety interlock circuit before fan start-up must be closed (e.g. burner swung shut, no fire in the windbox). The air dampers are run to the purge positions, then the post-purge time starts. At the end of the post-purge time, the combustion air fan is switched off and the air dampers are closed.

Post-purging is also carried out in the event of a combustion air pressure or purge position fault.

If the burner is switched on again during the post-purge sequence, the post-purge sequence is aborted and the purge sequence is started from the beginning with all the required safety prompts.

Post-purging with flue gas recirculation is performed in accordance with the parameterization with or without Staged purge sequence.

Post-purging of the furnace is only performed if the "combustion air fan" safety interlock circuit is closed (e.g. burner swung shut and no fire in the windbox).

Properties

Type

Selection parameter

[0] No post-purging
[1] Post-purging

Reference

1026

DOC-719769223