Operation mode
Activate fuels
Load shut-off limit during burner stop
Channel selection for this operation mode
Burner direct start / direct stop
Start additional fuel as of load position
Stop additional fuel as of load position
Primary fuel
Load position MAX start secondary fuel
Load position MIN start secondary fuel
Low-load position fuel A [Digit]
Low-load position fuel B [Digit]
Pilot Burner Function
Operation mode selected
Parameter
Description
A disconnection capacity [%] can be adjusted for every operation mode. The burner is switched off when the burner capacity drops below the disconnection capacity in the stop sequence.
The blow-out sequence for the oil gun is only started in the low-load position. This means: If the burner isn't switched off in the low-load position, then blow out of the oil gun is delayed until the burner has reached the low-load position. When the load drops below the disconnection capacity, only the igniter is put into operation and the fuel valves are closed until the low-load position is reached.
Properties
Floating point
0
100
%
Reference
6025; 6026; 6027; 6028; 6029; 6030; 6031; 6032
DOC-729012378