Load shut-off limit during burner stop

Parameter

Description

A disconnection capacity [%] can be adjusted for every operation mode. The burner is switched off when the burner capacity drops below the disconnection capacity in the stop sequence.

Note

The blow-out sequence for the oil gun is only started in the low-load position. This means: If the burner isn't switched off in the low-load position, then blow out of the oil gun is delayed until the burner has reached the low-load position. When the load drops below the disconnection capacity, only the igniter is put into operation and the fuel valves are closed until the low-load position is reached.

Properties

Type

Floating point

Min

0

Max

100

Unit

%

Reference

6025; 6026; 6027; 6028; 6029; 6030; 6031; 6032

DOC-729012378