HMI compound curve 2

Parameter

Description

In addition to the compound participants, Function blocks: [03] HMI Curve can be specified. These are adjusted on the fuel-air ratio side in parallel with the compound participants. This parameter refers to a function block of the type HMI curve.

The use of the HMI curves occupies the free spaces on the fuel-air ratio side. If 8 compound participants are available, no curve can be adjusted in addition.

Positioning on the fuel-air ratio side

The assignment via parameter and the ID of the function block offers an additional option:

Example

Function block ID = 146

In this case, position C6 is used as a priority for this curve. This means that the last position of the ID is taken and an attempt is made to position at this point. If the position is occupied, the first free position starting from C1 is used.

Purge/Ignition

The curves cannot be adjusted for ignition and purge position. The behavior during these times must be solved differently (e.g. controller special positions)

Properties

Type

Selection parameter

Reference

4746; 4747; 4748; 4749; 4750; 4751; 4752; 4753

DOC-721656471