Start oil pump

Parameter

Description

Properties

Type

Selection parameter

[0] Together with the combustion air fan

The oil pump is switched on and off together with the combustion air fan (e.g. screw pump).

[1] 5s before opening of the fuel valves.

The oil pump is switched on 5 s before opening of the fuel valves and is switched off together with the fuel valves (e.g. gear pump).