Cooling air: Pressure: MIN

Digital channel

Description

The normal cooling program expects the "Cooling air pressure MIN" = TRUE signal within 90 seconds.

If the signal is absent after this time, then the normal cooling program enters a fault state and the emergency cooling program is started.

Digital channel

Type

Input

ID

65

TRUE

> MIN

FALSE

< MIN

Reference

DOC-727703853