DFT: Emergency operation: External release

Digital channel

Description

This channel releases emergency operation. It must be TRUE so that emergency operation can be activated.

The constant value Constant ON can be set to TRUE for this channel. This ensures that emergency operation is always activated as soon as a safety shut-off occurs for one of the burners.

Digital channel

Type

Input

ID

133

TRUE

Released

FALSE

Not released

Reference

DOC-727617427