Description
If the burners are in single manual mode (each burner can be moved individually), this parameter is used to activate the triggering of a shutdown on fault if the load difference exceeds the configured value.
Note
As a rule, it makes no sense to activate this parameter because a value is normally set in the low percentage range for the maximum load difference so that a safety shut-off is triggered immediately in case of larger load differences between the two burners.