DFT: Single Manual Mode: Trip at load load difference

Parameter

Description

If the burners are in single manual mode (each burner can be moved individually), this parameter is used to activate the triggering of a shutdown on fault if the load difference exceeds the configured value.

Note

As a rule, it makes no sense to activate this parameter because a value is normally set in the low percentage range for the maximum load difference so that a safety shut-off is triggered immediately in case of larger load differences between the two burners.

Properties

Type

Yes/No

Reference

3066

DOC-727614343