Digital channels: Example: Output channel

Example: Control system of the combustion air fan

As soon as the burner is started, the combustion air fan should also be started.

For this purpose, the digital channel ("Start combustion air fan" = channel 316) is required. The channel is set to "TRUE" for a start request of the fan.

The figure below illustrates this example:

The digital channel required for this example must be configured as follows:

Digital channel 316
Field Setting
Channel ON ON
Channel is OUTPUT
Master-ID CAN-1
Node-ID 60
Value-ID 8

DOC-726564610