Defines the deviation between position feedback and setting value beyond which the actuator begins to move in continuous operation.
The numerical value of this parameter must be entered in standardized form (0 = 0%, 2000 = 100%).
Example
Setting value: "50 %" (corresponds to 1000 in the standardization).
Position feedback: "25 %" (corresponds to 500 in the standardization)
The current deviation corresponds to: 50 % - 25 % = 25 %,
The current deviation corresponds to standardized: 1000 - 500 = 500.
If the parameter is set to "100", for example, continuous operation starts at and above a deviation of 5%.