Controller: 3-point step: TSC-PULS

Parameter

Description

Defines the deviation between position feedback and setting value beyond which pulse mode begins.

The numerical value of this parameter must be entered in standardized form (0 = 0%, 2000 = 100%)

Example

Setting value: "50 %" (corresponds to 1000 in the standardization).

Position feedback: "25 %" (corresponds to 500 in the standardization)

The current deviation corresponds to: 50 % - 25 % = 25 %,

The current deviation corresponds to standardized: 1000 - 500 = 500.

If the parameter is set to "100", for example, pulse mode starts at and above a deviation of 5%.

Properties

Type

Integer

Min

0

Max

10000

Reference

DOC-726416876