Defines the deviation between position feedback and setting value beyond which pulse mode begins.
The numerical value of this parameter must be entered in standardized form (0 = 0%, 2000 = 100%)
Example
Setting value: "50 %" (corresponds to 1000 in the standardization).
Position feedback: "25 %" (corresponds to 500 in the standardization)
The current deviation corresponds to: 50 % - 25 % = 25 %,
The current deviation corresponds to standardized: 1000 - 500 = 500.
If the parameter is set to "100", for example, pulse mode starts at and above a deviation of 5%.