Pump station [1 - 4]: Pressure: Switch: MIN: On delay

Parameter

Description

The generation of the "Pressure < MIN" alarm is suppressed by this time. Here, you should adjust the time required by the pump after the start request to build up the minimum pressure. If the value 0 is adjusted, no monitoring takes place.

Properties

Type

Integer

Min

0

Max

3600

Unit

s

Reference

4341; 4342; 4343; 4344

DOC-724072183