Pump station [1 - 4]: Pumps: Change-over: Automatic according to operating duration

Parameter

Description

If the parameterized operating duration of the current running pump has expired, the standby pump becomes the main pump. With each manual pump switch or switch due to the operating duration, the timer is reset. However, this does not apply to pump starts and stops in manual mode.

Alarm-drive switching also does not reset the timer for operating duration.

If the parameter is set to 0, no automatic switch takes place.

Properties

Type

Integer

Min

0

Max

40000

Unit

h

Reference

4345; 4346; 4347; 4348

DOC-723383317