Pump station [1 - 4]: Designation

Every pump control system can be individually named. Predefined texts are available for selection (e.g. "Feed water"). The freely parameterizable texts (ID >5000) can also be used. If you use a freely parameterizable text is used, all required alarm messages must also be created.

Predefined selection:

[3000]: "Feed water"

This results in the following alarm numbers:

  • [4100]: "Feed water pump 1 not in operation"

  • [4101]: "Feed water pump 1 pressure < MIN"

  • [4102]: "Feed water pump 1 motor protection"

  • [4103]: "Feed water pump 2 not in operation"

  • [4104]: "Feed water pump 2 pressure < MIN"

  • [4105]: "Feed water pump 2 motor protection"

[3001]: "Oil"

This results in the following alarm numbers: [4106,4111]

[3002]: "Heavy oil"

This results in the following alarm numbers: [4112,4117]

[3003]: "Circulation"

This results in the following alarm numbers: [4118,4123]

Dynamic selection (freely parameterizable texts with ID >5000)

When texts are entered manually, the name (here as an example: hydrogen) must be defined block-wise together with the alarms.

[5010]: "Hydrogen"

This results in the following alarm numbers:

  • [5011]: "Hydrogen pump 1 not in operation"

  • [5012]: "Hydrogen pump 1 pressure < MIN"

  • [5013]: "Hydrogen pump 1 motor protection"

  • [5014]: "Hydrogen pump 2 not in operation"

  • [5015]: "Hydrogen pump 2 pressure < MIN"

  • [5016]: "Hydrogen pump 2 motor protection"