Description
Note
Only available for se@vis Land V3.00 as of Version V3.30.00.00
By linking multiple function block of this type (also referred to below as "status"), you can define automatic changes of operation mode.
Each status defines a burner status: e.g. "[M1] Oil", "[M5] Oil/Biogas", "[M8] Biogas" etc.
The linkage of multiple statuses is called a sequence.
Note
A sequence must begin with "Burner OFF".
A sequence always ends with a target operation mode (e.g. "[M8] Biogas").
If the system is in a configured status and the function block has a release, different conditions can trigger a switch to a different status (e.g. from "[M1] Oil" to [M5] Oil/Biogas):
- Next
-
The next status in the direction of the target operation mode.
- Fall Back
-
The status to which the system is to switch back by default if operating conditions are not met. "Fall back" removes itself from the target operation mode.
- Stop
-
If the system objective is to shut off the main combustion, there is an option to use a "Stop" status to trigger a shut-off (e.g. when shutting off the burner using a different fuel to that used to start the burner).