..
FSC input/output configuration
Second FSC available
FSC configuration for digital inputs
FSC configuration for digital outputs
The digital input and output signals are assigned to the safety-relevant digital inputs and outputs via parameters. Separate defined assignments are available for inputs and outputs.
The seavis FSC features
12 safety-relevant digital inputs,
8 safety-relevant digital outputs and
1 analog input (not safety-relevant).
The FSC-01 is required for the automatic firing sequence controller and the compound control system.
The FSC input and output configurations have been optimized for the following assignments of fuels to fuel types:
Fuel 1: Liquid fuels
Fuel 2: Gaseous fuels
Analog input (not safety-relevant)
The analog input of the FSC-01 is used for actual value of the load control (e.g. boiler pressure, boiler temperature), or for the external load demand. The analog input scaled from (0) 4 to 20 mA to (0) 400 to 2000 digits.
Parameterization
The input and output configuration is selected with the help of a wizard that provides an overview of all available inputs and outputs:
Wizard for selecting the FSC input and output configuration.
Selection of input configurations.
Selection of output configurations.
The input and output configuration selections only offer the options that are possible based on the current configuration. However, if you need to select other configurations, you can insert the check mark here. You can then select under (1) and (2) from all configurations.
see Second FSC available
All available inputs in the currently selected input configuration (1).
All available outputs in the currently selected output configuration (2).
If the input configuration contains inputs for the FSC-02, these are listed here.
If the output configuration contains outputs for the FSC-02, they are listed here.
See also
DOC-729501782