-
[Type]
Revolution counter
-
This parameter can be used to count the revolutions by timing instead of using the limit position of the soot blower. To do this, the set revolution time is taken as the basis (number of revolutions = time / revolution time). Monitoring, whether the soot blower has actually completed the corresponding number of revolutions, is not possible in this case.
If the revolutions are counted by the limit position, stopping may be switched off when the limit is reached (reduces relay switching cycles). This is not possible when revolutions are counted by timing.
0 |
Function switched off |
1 |
revolutions counted using the limit position with stop for each revolution. |
2 |
Revolutions counted using the limit position without stopping. |
3 |
Revolutions counted using the revolution time without stopping. |
-
[Rn]
Revolutions: Number
-
This parameter is used to set the number of revolutions of the soot blower for each start process. Each revolution is monitored via the set time. If the time has elapsed and the soot blower has still not reached the limit position, an alarm is triggered.
-
[Rt]
Revolution: Duration
-
This parameter sets the time which the soot blower requires for one complete revolution.
-
[DI 1]
Start
-
An ascending edge is expected as start signal.
-
The input signal is not optional and must be parameterized.
-
If an external release is available and an ascending edge was detected at the input, the soot blowing sequence is started.
-
The ascending edge at the input resets any existing faults before start-up (if this is possible).
-
If several modules are switched in succession, this input must be connected to the output DO 7 of the module switched beforehand.
-
[DI 2]
External release
-
A TRUE permanent signal is expected at the input.
-
The input signal is optional. If the channel ID is parameterized to 0 or the parameterized channel is switched off, the signal is set internally to TRUE.
-
If the input is activated, the soot blower control unit is released.
-
If the release is withdrawn during operation, the soot blower control unit is reset to the initialization state.
-
If the steam shut-off valve is open, it is closed again.
-
If the revolutions are counted by the limit position, the soot blower motor is not switched off until the limit position is reached. This is specified by the hardware structure (self-retaining) and cannot be influenced by the software.
-
[DI 3]
Operating status
-
A TRUE permanent signal is expected at the input.
-
The input signal is optional. If the channel ID is parameterized to 0 or the parameterized channel is switched off, the signal is internally simulated and set to TRUE at a given time.
-
If the soot blower is activated, the input must be set within 2s.
-
If the soot blower is started but the input is not set or not set in good time, the error is signaled by the output DO 1.
-
[DI 4]
Overload protection status
-
A FALSE permanent signal is expected at the input.
-
The input signal is optional. If the channel ID is parameterized to 0 or the parameterized channel is switched off, the signal is set internally to FALSE.
-
Wire breakage protection must be obtained by inverting the channel.
-
If the overload protection switch is triggered or manually switched off, the input is activated.
-
A detected error is signaled by the output DO 1.
-
[DI 5]
Steam valve: Status
-
A TRUE permanent signal is expected at the input.
-
The input signal is optional. If the channel ID is parameterized to 0 or the parameterized channel is switched off, the signal is internally simulated and set to TRUE at a given time.
-
The input is occupied by the "Limit position open" contact of the steam shut-off valve.
-
If the steam shut-off valve is activated, the input must be activated within 2s.
-
If the input is not activated or not activated in good time, the error is signaled by the output DO 6.
-
[DI 6]
Steam pressure: > MIN
-
A TRUE permanent signal is expected at the input.
-
The input signal is optional. If the channel ID is parameterized to 0 or the parameterized channel is switched off, the signal is internally simulated and set to TRUE at a given time.
-
The input is occupied by the "> MIN" contact of the steam pressure switch.
-
If the limit switch "steam shut-off valve open" is actuated, the input must be activated within 3s.
-
If the input is not activated or not activated in good time, the error is signaled by the output DO 2.
-
Due to the wire breakage protection, the contact must be a "normally open contact" and close at steam pressure > MIN.
-
[DI 7]
Revolution: Limit position
-
An ascending edge is expected at the input.
-
If the control system is configured as Type 1 or 2, the input signal is not optional and must be parameterized.
-
If the control system is configured as Type 3, the input signal is not used.
-
The control types 1 and 2 use the limit position "soot blower rotation" for counting revolutions. The soot blower reaches the limit position after each complete revolution. Pressing the limit switch generates an ascending edge at the input, causing the revolutions counter to increase by 1.
-
[DI 8]
Fault: External
-
A FALSE permanent signal is expected at the input.
-
The input signal is optional. If the channel ID is parameterized to 0 or the parameterized channel is switched off, the signal is set internally to FALSE.
-
If the input is activated, the fault is connected through to the output "collective alarm" (required to link modules).
-
[DI 9]
Acknowledge: Fault
-
An ascending edge is expected as acknowledgment signal.
-
The input signal is not optional and must be parameterized.
-
If the input is set (impulse), all error messages detected and saved by the software are reset.
-
The overload protection error cannot be reset, as this depends on the position of the protection switch.