[28] Volume flow orifice plate
Function blocks
Description
This function block calculates the volume flow rate of a hydraulic system based on the differential pressure of an orifice.
Function block parameters
Function block inputs
Fixed value.
The flow coefficients are used to consider all losses which occur when a fluid flows through an orifice plate. The flow coefficient is usually within a range between 0.7 and 0.9.
Fixed value
Example of circular orifice plate opening: A[cm²] = π x (r[mm])² / 100
Water has a density of 997.
Analog channel
"Pressure downstream of the orifice plate (p1)" minus "Pressure upstream of the orifice plate (p2)"
Function block outputs
Q = 3600 x a x (A/10000) x √( 2/ρ x dP )
Reference
Vol.flow orifice
DOC-723985274