FSM 02000L setup

The following default parameters must be configured and checked for the motor.

Note

Only change the parameters for the compound channel to which the FSM is assigned. In the list below, search for the required compound channel and note the parameterization instructions.

Compound channel C1
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2132 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2133 1 Digit
TPS pulse time 2134 30 ms
TPS break time 2135 400 ms
Minimum Running Time of Channel Setpoint 2137 See description "Adjust minimum running time for channel setpoint" further below.
Tolerance band limit 2143 15 Digit
Monitoring band limit 2144 30 Digit
Compound channel C2
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2160 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2161 1 Digit
TPS pulse time 2162 30 ms
TPS break time 2163 400 ms
Minimum Running Time of Channel Setpoint 2165 See description "Adjust minimum running time for channel setpoint" further below.
Tolerance band limit 2171 15 Digit
Monitoring band limit 2172 30 Digit
Compound channel C3
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2188 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2189 1 Digit
TPS pulse time 2190 30 ms
TPS break time 2191 400 ms
Minimum Running Time of Channel Setpoint 2193 See description "Adjust minimum running time for channel setpoint" further below.
Tolerance band limit 2199 15 Digit
Monitoring band limit 2200 30 Digit
Compound channel C4
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2216 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2217 1 Digit
TPS pulse time 2218 30 ms
TPS break time 2219 400 ms
Minimum Running Time of Channel Setpoint 2221 See description "Adjust minimum running time for channel setpoint" further below.
Tolerance band limit 2227 15 Digit
Monitoring band limit 2228 30 Digit
Compound channel C5
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2244 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2245 1 Digit
TPS pulse time 2246 30 ms
TPS break time 2247 400 ms
Minimum Running Time of Channel Setpoint 2249 See description "Adjust minimum running time for channel setpoint" further below.
Tolerance band limit 2255 15 Digit
Monitoring band limit 2256 30 Digit
Compound channel C6
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2272 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2273 1 Digit
TPS pulse time 2274 30 ms
TPS break time 2275 400 ms
Minimum Running Time of Channel Setpoint 2277 See description "Adjust minimum running time for channel setpoint" further below.
Tolerance band limit 2283 15 Digit
Monitoring band limit 2284 30 Digit
Compound channel C7
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2300 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2301 1 Digit
TPS pulse time 2302 30 ms
TPS break time 2303 400 ms
Minimum Running Time of Channel Setpoint 2305 See description "Adjust minimum running time for channel setpoint" further below.
Tolerance band limit 2311 15 Digit
Monitoring band limit 2312 30 Digit
Compound channel C8
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2328 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2329 1 Digit
TPS pulse time 2330 30 ms
TPS break time 2331 400 ms
Minimum Running Time of Channel Setpoint 2333 See description "Adjust minimum running time for channel setpoint" further below.
Tolerance band limit 2339 15 Digit
Monitoring band limit 2340 30 Digit
Compound channel C9
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2353 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2354 1 Digit
TPS pulse time 2355 30 ms
TPS break time 2356 400 ms
Compound channel C10
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2360 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2361 1 Digit
TPS pulse time 2362 30 ms
TPS break time 2363 400 ms
Compound channel C11
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2367 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2368 1 Digit
TPS pulse time 2369 30 ms
TPS break time 2370 400 ms
Compound channel C12
Parameter name Parameter-ID Value to be set
TPS limit continuous operation 2374 See description "Adjust TSC limit value of continuous operation" further below.
TPS limit pulse operation 2375 1 Digit
TPS pulse time 2376 30 ms
TPS break time 2377 400 ms

Adjust "TSC limit value of continuous operation"

You must check this parameter and adjust it if required.

  1. Adjust the parameter to the initial value of 15 digit.

  2. Move the FSM on the HMI, e.g., to the purge position or to the upper range limit

  3. Let the FSM move to a different value such as the lower range limit or a load point. You can do this by pressing "Cancel" or selecting a load point. You cannot move the FSM manually using the plus and minus buttons.

  4. The FSM moves in continuous operation in the direction of the setpoint. As soon as continuous operation is exited, the FSM starts to pulse.

    The number of pulses must be at least 1 and a maximum of 3.

    If the number is correct, you are finished.

    If the number of pulses is more than 3, reduce the parameter "TSC continuous operation limit value" by 1 digit.

    If the number of pulses is less than 1, increase the parameter "TSC continuous operation limit value" by 1 digit.

    Then begin again with step 2 and check the number of pulses again.

Adjust "Minimum running time of channel setpoint"

"Minimum running time of channel setpoint" = "Running time of the FSM" minus "3 seconds".

You can read the running time of the FSM on the HMI on the respective compound channel side. This is also designated "t motor".

Example

"Running time of the FSM (t motor)" = 43 s

"Minimum running time of channel setpoint" = 43 s - 3s = 40 s

DOC-721831844