FSC-IO
FSC-IO uses feedback curve
Offset band monitoring
Scan time for attenuation of the feedback signal
Parameter
Description
You can activate a feedback curve for each compound channel which controls an FSC-IO module. With the feedback curve, the measured actual position value is saved in addition to the position setpoint for each load point. The tolerance band and the monitoring band are monitored with the saved actual position values.
When you activate the feedback curve for a channel, the "band monitoring offset" will automatically be deactivated for this channel.
For polling the MAX, purging and ignition positions, the associated actual values are saved separately.
The analog feedback values can be smoothed via an adjustable attenuation.
The feedback curve should only be used when comparing of the channel setpoint and the channel actual value isn't required.
For detailed information, consult the "System Manual for seavis compact part 4: Service and Commissioning" (2-7931-8084) in the "Putting drives into operation" chapter.
Properties
Yes/No
Reference
1090; 1106; 1122; 1138; 1154; 1170; 1186; 1202
DOC-720689790