FSC-IO

Set the tolerance band and monitoring band limits such that safe operation is possible and the firing limit values are complied with.

If compound channels control FSC-IO AO/AI modules, then configure the HOST address as follows:

Compound channel 1 2 3 4 5 6 7 8
FSC-IO 4RO/1AO 40 41 42 43 44 45 46 47
FSC-IO 4DI/1AI 20 21 22 23 24 25 26 27

Example

If you want to use compound channel 5 as a permanent channel for a speed controller, you must set the HOST address 44 for FSC-IO 4RO/1AO and the HOST address 24 FSC-IO 4DI/1AI.

Activate the dynamic test for the corresponding compound channels as well.

See also

DOC-720625784