..
Valve test system
Type
F [1 - 3]: VPS: Load valve
F [1 - 3]: VPS: Load time
F [1 - 3]: VPS: Relief valve
F [1 - 3]: VPS: Relief time
VPS: Calculating the testing times
F [1 - 3]: VPS: Fuel valve 1: Proof time
F [1 - 3]: VPS: Fuel valve 2: Proof time
F [1 - 3]: VPS: Valid time
F [1 - 3]: VPS: Fuel valve 2: Delayed close
Parameter
Description
Adjust the test times of the gas valves to the size of the test segment. Ensure that a leak of 0.1 % of the burner gas consumption at maximum firing heat capacity, but at least 50 dm³/h, is detected reliably.
For information on this topic, refer to the "Sensitivity limit" section of DIN EN 1643.
The permissible leakage rate must be agreed with the technical expert and the plant authorities of the firing plant. We recommend that a leakage rate of 200 dm³/h should not be exceeded.
Properties
Integer
0
32400
s
Reference
2115; 2006; 2120
DOC-719834338