RECI: Load limitation cold start

Parameter

Description

If a channel in the compound is assigned to FGR, the load setpoint is limited to the value set here via the digital input "Flue gas recirculation release" (flue gas temperature > MIN), and the FGR channels remain in the ignition position (= closed).

Properties

Type

Integer

Min

0

Max

100

Unit

%

Reference

2004

DOC-719825811