Compound
Current burner load
Load curve: Current position
Burner load: Physical scaling
Burner load: Physical unit
Full load: Load position
Full load: Physical value
Minimum running time of compound control
Load setpoint response threshold
Dynamik Test
Fuel and Air Setpoints for Load Changes
Maximum load difference fuel > air
Minimum load difference air > fuel
Maximum load difference air > fuel
Load setpoint Overshoot
Parameter
Description
Defines the maximum load difference by which the fuel setpoint can exceed the air setpoint.
This parameter is set at the factory. Change these parameters only after consultation with the electrical design department of SAACKE.
Fuel / air setpoint development in case of load changes
Time in s
Load setpoint in digit
Compound control system load setpoint
Air channel load setpoint
Fuel channel load setpoint
For small load changes, the load difference has virtually no influence on the fuel/air setpoints and the channels run almost in parallel.
With large positive load changes, the fuel setpoint is reduced by the minimum load difference compared to the air setpoint.
With large negative load changes, the air setpoint is increased by the minimum load difference compared to the fuel setpoint.
The maximum load difference limits the air excess during long periods of continuous load changes if
the air channels follow an increasing load faster than the fuel channels or
the fuel channels follow a decreasing load faster than the air channels
The load difference between the fuel and air setpoint is calculated dynamically depending on the speed of the load change.
Properties
Integer
0
20
Digit
Reference
2035