Ignition flame extraneous light: No monitoring during burner operation

Parameter

Description

Note

This function may only be deactivated if the applicable standards and regulations don't prohibit this.

Properties

Type

Yes/No

[Yes]

The safety shut-off and the start disable are deactivated by the ignition flame extraneous light test. The alarm message (1032) "Ignition flame: extraneous light detected" is also output if this parameter is set to TRUE.

Reference

1057

DOC-729019678