F [1 - 3]: VPS: Load time

Parameter

Description

2116 VPS1: Charging time [s]
2007 VPS2: Charging time [s]
2121 VPS3: Charging time [s]

Maximum opening time setting for the valve with which the pressure in the test segment is automatically built up during the valve test.

Important

If you use fuel valve 1 for charging, a maximum of 3 seconds is permissible (EN 676).

Properties

Type

Integer

Min

0

Max

30

Unit

s

Reference

2116; 2007; 2121

DOC-719833615