Valve test system
Type
F [1 - 3]: VPS: Load valve
F [1 - 3]: VPS: Load time
F [1 - 3]: VPS: Relief valve
F [1 - 3]: VPS: Relief time
VPS: Calculating the testing times
F [1 - 3]: VPS: Fuel valve 1: Proof time
F [1 - 3]: VPS: Fuel valve 2: Proof time
F [1 - 3]: VPS: Valid time
F [1 - 3]: VPS: Fuel valve 2: Delayed close
Parameter
Description
Maximum opening time setting for the valve with which the pressure in the test segment is automatically built up during the valve test.
If you use fuel valve 1 for charging, a maximum of 3 seconds is permissible (EN 676).
Properties
Integer
0
30
s
Reference
2116; 2007; 2121
DOC-719833615