F [1 - 3]: VPS: Relief time

Parameter

Description

Opening time for the valve with which the pressure in the test segment is automatically relieved during the valve test.

If you use fuel valve 2 for pressure relief, a maximum of 3 seconds is permissible (EN 676). That means:

Properties

Type

Integer

Min

0

Max

30

Unit

s

Reference

2114; 2005; 2119

DOC-719832909