F [1 - 3]: VPS: Relief valve

Parameter

Description

Properties

Type

Selection parameter

[0] Is a hand valve

If a hand valve is used, fuel valve 2 can be closed with delay for the automatic pressure relief of the test segment.

[1] Is main gas valve 2

If the pressure relief of the test segment of one fuel is to be performed using fuel valve 2, the valve test after shut-down is permitted only together with post-purging <varname>1026</varname>=1. For information on this topic, refer to the "Valve monitoring system" section of DIN EN 676.

[2] Is a separate valve open when de-energized

Automatic pressure relief of the test segment is performed with a separate relief valve "open when deenergized".

[3] Is a separate valve closed when de-energized

Automatic pressure relief of the test segment is performed with a separate relief valve "closed when deenergized".

Reference

DOC-719830650