Valve test system
Type
F [1 - 3]: VPS: Load valve
F [1 - 3]: VPS: Load time
F [1 - 3]: VPS: Relief valve
F [1 - 3]: VPS: Relief time
VPS: Calculating the testing times
F [1 - 3]: VPS: Fuel valve 1: Proof time
F [1 - 3]: VPS: Fuel valve 2: Proof time
F [1 - 3]: VPS: Valid time
F [1 - 3]: VPS: Fuel valve 2: Delayed close
Parameter
Description
[0 ; 240] corresponds (x0,1) [0 ; 24] hours
If the valve test was completed successfully, then the burner is started within the configured validity time without a renewed valve test in gas firing operation mode.
A successfully completed valve test is invalidated,
when the respective validity time has expired.
if a fuel valve for fuel 1 is opened during the VPS1 validity time.
if one of the fuel valves for fuel 2 is opened during the VPS2 validity time.
after the supply voltage has been restored.
Properties
Integer
0
240
[x 0.1 h]
Reference
2118; 2010; 2108
DOC-719827147