F [1 - 3]: VPS: Valid time

Parameter

Description

[0 ; 240] corresponds (x0,1) [0 ; 24] hours

If the valve test was completed successfully, then the burner is started within the configured validity time without a renewed valve test in gas firing operation mode.

A successfully completed valve test is invalidated,

  • when the respective validity time has expired.

  • if a fuel valve for fuel 1 is opened during the VPS1 validity time.

  • if one of the fuel valves for fuel 2 is opened during the VPS2 validity time.

  • after the supply voltage has been restored.

Properties

Type

Integer

Min

0

Max

240

Unit

[x 0.1 h]

Reference

2118; 2010; 2108

DOC-719827147